excavation and backfilling. There shall be a minimum of 2 continuity bonds
between each structure and other than welded or threaded joints.
Electrical continuity shall be tested across joints with other than welded
or threaded joints and across metallic portions of sewage lift stations and
water booster stations.
2.4.19.1
the criteria of protection. Alternate methods may be used when approved.
2.4.19.2
Stray Current Measurements
Stray current measurements shall be performed as indicated. Alternate
methods may be used when approved. The stray current test report shall
indicate location of test, type of pipes tested, method of testing, [_____].
2.4.20
Electrical Isolation of Structures
Isolating fittings, including isolating flanges and couplings, shall be
installed above ground or in a concrete hand hole. As a minimum, isolating
flanges or unions shall be provided at the following locations:
a.
Connection of new piping to existing pipes.
b.
Pressure piping under floor slab to a building.
Additionally, isolation shall be provided between new pipe lines and
foreign pipes that cross the new lines within 3 m 10 feet.
2.5
MAGNESIUM ANODES
Weights and dimensions of magnesium anodes shall be approximately as
follows:
TYPICAL MAGNESIUM ANODE SIZES
NOMINAL GROSS
NOMINAL
APPROX.
WT kg PACKAGED
NOMINAL PACKAGE
WT. kg.
SIZE (mm)
DIMENSIONS (mm)
1.4
76
X
76
X
127
3.6
133
X
133 X 203
2.3
76
X
76
X
203
5.9
133
X
133 X 286
4.1
76
X
76
X
356
12.3
133
X
508
5.5
102
X
102
X
305
14.5
191
X
457
7.7
102
X
102
X
432
20.5
191
X
610
14.5
127
X
127
X
521
30.9
216
X
711
22.7
178
X
178
X
406
45.5
254
X
610
TYPICAL MAGNESIUM ANODE SIZES
NOMINAL GROSS
NOMINAL
APPROX.
WT LBS PACKAGED
NOMINAL PACKAGE
WT. LBS.
SIZE (IN)
DIMENSIONS (IN)
3
3X3X
5
8
5 1/4 X 5 1/4 X 8
5
3X3X
8
13
5 1/4 X 5 1/4 X 11 1/4
SECTION 13112A
Page 24