Enclosures shall be of 3.1 mm 11 gauge steel or heavier, with an accessible
drain plug. The oil level shall be clearly marked. The lid shall be
hinged and have quick release clamps to secure it in closed position. A
stop shall limit the swing of the lid when opened. A compressible, oil
resistant, positive sealing gasket shall be provided. The gasket shall
return to its original shape upon release of lid pressure. The gasket shall
be attached to the tank or lid and joints shall be free of gaps. Base
mounting using 102 mm 4 inch high channels shall be provided. Conduits
entering the enclosure shall be internally sealed and shall enter or exit
above the oil fill line.
2.3
COKE BREEZE
2.3.1
Calcined Petroleum Coke Breeze (Dry)
Breeze shall conform to the following requirements:
2.3.1.1
Electrical Resistivity
Resistivity shall not exceed 1 milliohm-meter (0.1 ohm-cm) Great Lake
Carbon C 12 A Test Method.
2.3.1.2
Bulk Density - 1044 to 1204 kg/cubic meter 65 to 75 lbs/cubic foot
Fixed Carbon - 99.0% or greater
Volatiles - 0.2% or less
Sizing - 100% less than 13 mm 1/2 inch
2.3.2
Metallurgical Coke Breeze (Processed)
Breeze shall conform to the following requirements:
2.3.2.1
Electrical Resistivity (Nominal)
a.
100 milliohm-meter (10 ohm-centimeter) Max., tightly compacted.
b.
100 milliohm-meter to 150 milliohm-meter, (10 to 15
ohm-centimeter,) lightly compacted.
c.
150 to 200 milliohm-meter, (15 to 20 ohm-centimeter,) loose.
2.3.2.2
Bulk density - 608 to 672 kg per cubic meter 38 to 42 pounds per cubic foot
Fixed Carbon - 80% or greater
Sizing - 100% less than 10 mm 3/8 inch
2.4
MISCELLANEOUS MATERIALS
2.4.1
Electrical Wire
2.4.1.1
Anode Connecting Wire
**************************************************************************
SECTION 13112A
Page 18