2.3.3
Self-Contained Refrigerant Systems
**************************************************************************
NOTE: Select mounting. Side-mounted units are
Top-mounted units are available in sizes up to 4 kW
**************************************************************************
Factory-fabricated in accordance with UL 427 for [side-wall] [top-wall]
mounting. Systems shall include a condensing unit mounted on the exterior
and a forced air evaporator mounted on the interior directly opposite.
2.4
**************************************************************************
NOTE: The following paragraph is for units
operating at below-freezing temperatures.
**************************************************************************
Provide condensate drain lines and drains below freezer floors with
electric heating cable, thermostatically controlled to maintain [_____]
degrees C F at zero flow rate. Cable shall be size [_____] to provide
[_____] watts per meter linear foot.
PART 3
EXECUTION
3.1
INSTALLATION
Installation procedures shall conform to NSF 7, and the manufacturer's
instructions. Submit a set of instructions covering both assembly of the
rooms and installation of the refrigeration equipment before starting
installation.
3.2
MANUFACTURER'S FIELD SERVICES
Furnish manufacturer's representatives who are trained to perform the
services specified. The representatives shall furnish and services on the
following matters:
a.
Erection, alignment, and testing.
b.
Charging equipment with refrigerant and oil.
c.
Starting equipment and training government personnel as to its
proper care, operation, and maintenance.
3.3
TESTS
Perform the tests for each room and provide everything required. Notify
be performed in the presence of a manufacturer's representative.
3.3.1
Start up and initially operate the systems upon completion of the
installation of the equipment and refrigerant piping. Adjust the safety
and automatic controls to place them in operation and sequence. Record
SECTION 13038
Page 7