b.
Door/jamb heater and temperature monitors/alarms.
c.
Evaporator fans, defrost elements, freezer fan door switch, and
drain line heaters.
2.13.10
Lamps
Food service equipment containing light fixtures shall have standard
appliance type bulbs or energy efficient appliance type bulbs as indicated
on the drawings. Exposed fluorescent lamps above or within a food zone
shall have plastic coated T-8 energy efficient lamps or standard lamps,
sleeved in plastic tube with end caps.
2.13.11
Steam Connection Provisions
Steam-injected equipment shall have a steam inlet globe control valve with
cold handle, relief valve, strainer, condensate gate valve, bucket steam
trap, and swing check valve. Compartment steam cookers shall have piping
manifolded from all compartment exhaust valves to a floor drain, floor
sink, or drain trench. Steam generators specified within this section
shall have automatic boiler blowdown and a cold water condenser. Separate
equipment, devices or components indicated to be connected to a
steam-generator, provided under this section, shall be provided with all
unions, ells, gate valves, nipples, brackets, clamps, etc., required for
the complete operating system for final connection. The steam supply
piping shall be insulated with 25 mm 1 inch fiberglass insulation (48
kg/cubic meter 3 pounds/cubic foot density) and shall have factory-applied
fire retardant. A full-length 1.6 mm (16 gauge) 16 gauge stainless steel
pipe enclosure with sloping top, jacket, and vapor barrier shall be
installed over steam lines.
2.14
COLOR
Color shall be [in accordance with Section 09915 COLOR SCHEDULE] [_____].
PART 3
EXECUTION
3.1
INSTALLATION
Equipment shall be installed at locations shown in accordance with NSF
Product Listing and the manufacturer's written instructions. The
Contractor shall make provision for the plumbing, heating, and electrical
connections and for equipment indicated as being furnished and installed by
the Government.
3.1.1
otherwise specified, exposed piping shall be [chromium-plated copper alloy]
3.1.2
Backflow Preventers
**************************************************************************
NOTE: Designers will show on the drawings all
locations where backflow preventers are required.
Backflow Preventers.
**************************************************************************