is limited to a certain lamp type. Medium pressure
lamps have an approximate life of 3 to 4000 hours,
while low pressure lamps have an approximate life of
7 to 10000 hours; certain proprietary, high
intensity lamps may have a life less than 2000 hours.
**************************************************************************
The Contractor shall be responsible for changing out lamps, ballasts, and
quartz tube wipers at the frequency recommended by the manufacturer during
the one year warranty period or as otherwise required. Lamps and ballasts
supplied as specified below, shall be provided in addition to the complete
set supplied for installation (following the warranty period) and those
installed as needed during the warranty period. The ozone generator
dielectrics shall be cleaned in accordance with the manufacturer's
recommendations immediately prior to the conclusion of the Contractor's
operating period; or after one year, if greater than one year after
startup, and at the conclusion of the Contractor's operating period.
3.13.2
Extra Materials
**************************************************************************
NOTE: Delete inapplicable portions of these
paragraphs. Coordinate this section with other
sections of the specifications to ensure there are
not conflicts regarding supplying consumables.
Verify the duration of the initial operating period,
which is generally 1 year.
**************************************************************************
The Contractor shall furnish the initial supplies to fill the vessels, as
well as all consumables during the startup, prove out, and initial
operation period. At the time the Contractor turns the plant over to the
long term Operation and Maintenance Contractor, the vessels storing
consumables such as LOX, hydrogen peroxide [and] [_____] shall be refilled
within [two] [five] days prior to the plant turn over.
3.13.2.1
Lamps
The Contractor shall provide a complete set of lamps that shall be reserved
for change out by the equipment supplier following the one year warranty
period. This extra set of lamps shall be delivered to the treatment
facility 60 days prior to the end of the one year warranty period and
installed by the Contractor. Lamp replacement during the one year warranty
period shall be provided by the supplier, as needed by the Contractor.
3.13.2.2
Spare Parts
The supplier shall provide, in addition to the lamps specified above, a
minimum of ten percent of each of the following items, or a minimum of two,
whichever is greater:
a.
Lamp ballasts
b.
Quartz sleeves
c.
End seals
d.
Socket connectors
SECTION 11377
Page 40