hypochlorinator is specified.
**************************************************************************
**************************************************************************
extended aeration type plants 0.88 L/s 20,000 GPD
and below and for plants in remote locations. Use
weekly charts for extended aeration type and step
aeration type above 0.88 L/s 20,000 GPD capacity
through 6.60 L/s 150,000 GPD capacity. Use daily
charts for extended aeration type and step aeration
type above 6.60 L/s 150,000 GPD capacity, and for
all complete mixing type plants.
**************************************************************************
**************************************************************************
NOTE: Insert electrical power characteristics.
**************************************************************************
**************************************************************************
NOTE: Delete requirements for signal transmission
to the chlorinator when hypochlorinator is specified.
**************************************************************************
The [transmitting] recorder-totalizer-indicator shall combine the functions
of recording, totalizing indicating within one case; shall read in liters
per second thousands of gallons per day in uniformly graduated units; and
shall have a range of from 5 to 150 percent of the average flow through the
plant. The chart, totalizer read-out, and indicator scale shall be visible
through a shatterproof clear window(s). Internal movements within the
instrument shall in no way interfere with taking of the differential
measurement. The mechanism shall not be affected by the intended end use
environment. The chart shall be 250 or 300 mm 10 or 12 inches in diameter
and shall rotate once [daily] [weekly] [monthly]. The chart drive shall be
[_____] phase, [_____] Hertz service. Totalizer shall read the total flow
in thousand liter thousand gallon units using only a whole power of 10
multiplier. [The signal transmission to the chlorinator shall be impulse
transmission shall be actuated by the output motion meter. Power shall be
[_____] volt, [_____] Hertz service.] The case shall be aluminum,
fiberglass, or painted steel and part of the meter. The unit shall be
weatherproof equipped with a sealed door for access to the mechanism, and
designed to prevent the accumulation of moisture or fog inside the case. A
suitable mounting stand shall be provided.
2.12.2.5
Charts for Recorder
One year's supply of charts and ink shall be furnished for recorder.
2.13
ELECTRICAL CONTROL SYSTEM COMPONENTS
2.13.1
General
**************************************************************************
NOTE: Specify outdoor type enclosure except when
enclosure will be located in a building.
**************************************************************************