Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control
approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for
the Government.] The following shall be submitted in accordance with
Section 01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Window units
Indicate the elevations of windows, half-size sections,
thicknesses and gages of metal, fastenings, proposed method of
anchoring, the size and spacing of anchors, details of
construction, method of glazing, mullion details, casings, sills,
trim, other related items, and installation details.
SD-03 Product Data
Window units
Fasteners
Accessories
SD-06 Test Reports
Air infiltration
Water infiltration
Mullion and transom bar wind load
1.3
QUALITY ASSURANCE
The requirements specified in this section govern where there is a
difference between this section and the referenced industry specifications.
1.3.1
Test Reports
1.3.1.1
Air and Water Infiltration Tests
ASTM E 283 and ASTM E 331. Air infiltration shall not exceed 0.8 L/s per
meter one-half cubic foot per minute per foot of crack length when
subjected to a static pressure of 75 Pa 1.56 pounds per square foot
(equivalent to a wind velocity of 40 km/hr 25 miles per hour). The amount
of water infiltration shall be "zero" when tested in accordance with ASTM E
331.
1.3.1.2
Mullion and Transom Bar Wind Load Tests
**************************************************************************
NOTE: Specify wind loading requirements in areas
subject to high wind velocities in excess of 110
km/hr 70 MPH; otherwise delete. The wind loading of
SECTION 11191
Page 6