1.4.3.10
PTFE-Pigmented Fluoropolyurethane Coating Materials
Provide manufacturer's certification of conformance to contract
requirements.
1.4.3.11
Coating System Component Compatibility
Provide certification from each manufacturer of components of the coating
system, epoxy primer, epoxy intermediate, and fluoropolyurethane topcoat,
that the supplied coating material is suitable for use in the specified
coating system. Each manufacturer shall identify the specific products,
including manufacturer's name, which their product may be used with. The
certification shall provide the name of the manufacturer that will provide
technical support for the entire system. When all coating materials are
manufactured by one manufacturer, this certification is not required.
1.4.3.12
Non-metallic Abrasive
Provide manufacturer's certification that the materials are currently
approved by the Naval Sea Systems Command and listed on the Qualified
Products List (QPL) for the specified materials.
1.4.3.13
Metallic Abrasive
Provide manufacturer's certification of conformance to contract
requirements and provide copies of test results.
1.4.4
Product Data
1.4.4.1
Roof Joint Sealant Instructions
Submit manufacturer's printed instructions including detailed mixing and
application procedures, minimum and maximum application temperatures, and
curing procedures. Include Materials Safety Data Sheets (MSDS) for
materials to be used at the job site in accordance with 29 CFR 1926.59.
1.4.4.2
Coating System Instructions
Submit manufacturer's printed instructions including detailed mixing and
application procedures, number and types of coats required, minimum and
maximum application temperatures, and curing procedures. Include Materials
Safety Data Sheets (MSDS) for materials to be used at the job site in
accordance with 29 CFR 1926.59.
1.5
DELIVERY AND STORAGE
Ship, store, and handle materials in accordance with SSPC PA 1, and as
modified in this Section. Maintain temperature in storage spaces between 5
and 24 degrees C 40 and 75 degrees F, and air temperature more than 3
degrees C 5 degrees F above the dew-point at all times. Inspect materials
for damage prior to use and return non-compliant materials to manufacturer.
immediately and notify the Contracting Officer. Expired materials may be
returned to manufacturer, tested, and if compliant, issued a shelf life
extension.
1.6
COATING HAZARDS
**************************************************************************
SECTION 09970
Page 15