Include descriptive literature, detailed specifications, and
available performance test data.
SD-05 Design Data
Calculations
SD-08 Manufacturer's Instructions
Glazed curtain wall system
Insulating glass
1.3
REQUIREMENT FOR DESIGN DATA
Submit structural and thermal calculations for complete wall assembly.
1.4
QUALITY ASSURANCE
1.4.1
Testing Requirements
**************************************************************************
NOTE: Revise this paragraph as necessary to cover
project requirements.
**************************************************************************
The components listed below shall have been tested in accordance with the
requirements below, and shall meet performance requirements specified.
a.
applicable publications referenced.
b.
Preformed Compression Gaskets and Seals:
ASTM C 864.
c.
Preformed Lock-strip Gaskets: ASTM C 542, modified as follows:
Heat age specimens seven days at 70 degrees C 158 degrees F, in
zipped or locked position under full design compression. Unzip,
cool for one hour, re-zip, and test lip seal pressure, which shall
be minimum 0.045 kilograms per linear millimeter 2.5 pounds per
linear inch on any extruded or corner specimen.
d.
Spandrel Glass:
e.
Porcelain Enamel: Acid resistance, color retention, and spall
f.
Anodized Finishes: Stain resistance, coating weight, and coating
thickness tests, ASTM B 136, ASTM B 137, and ASTM B 244,
respectively.
g.
Insulating Glass: ASTM E 546 or ASTM E 576 at [minus 29 degrees C
20 degrees F] [_____], no frost or dew point.
1.4.2
Mockup
**************************************************************************
NOTE: Size of project and system specified will
determine whether mock-ups are necessary. Complete
information should be given concerning extent,
SECTION 08900
Page 10