USACE / NAVFAC / AFCESA
UFGS-08162 (August 2001)
------------------------------
Preparing Activity: NAVFAC
Superseding
UFGS-08162 (September 1999)
UNIFIED FACILITIES GUIDE SPECIFICATIONS
References are in agreement with UMRL dated 23 June 2005
Latest change indicated by CHG tags
**************************************************************************
SECTION 08162
SLIDING FIRE DOORS
08/01
**************************************************************************
NOTE: This guide specification covers the
requirements for horizontal and vertical sliding
steel-covered composite, hollow-metal, corrugated
sheet metal, and tin-clad fire doors.
Comments and suggestions on this guide specification
are welcome and should be directed to the technical
proponent of the specification. A listing of
technical proponents, including their organization
designation and telephone number, is on the Internet.
Recommended changes to a UFGS should be submitted as
a Criteria Change Request (CCR).
Use of electronic communication is encouraged.
Brackets are used in the text to indicate designer
choices or locations where text must be supplied by
the designer.
**************************************************************************
**************************************************************************
NOTE: Fire rated doors of the swinging hollow
metal, wood, coiling, and overhead types are not
covered in this guide specification and should be
covered in the respective section covering the
particular type door.
**************************************************************************
**************************************************************************
NOTE: On the drawings, show:
1.
Rough opening for each door.
2.
Required headroom for level or inclined track.
3.
Fire rating classification for each door.
4.
Type of door operation, i.e. level track,
SECTION 08162
Page 3