Intercommunication system
Submit for overall system and for each major component.
Illustrate how each item of equipment will function in the system
and include an overall system schematic indicating relationship of
intercommunication units on one diagram identifying type, size,
and number of wiring, conduits and each major component.
SD-03 Product Data
Materials and equipment for Type [1] [2] [3] system
[Paging system equipment]
[Public address and monitoring system equipment]
Cables and raceways
Surge protection
SD-10 Operation and Maintenance Data
Intercommunication system, Data Package 5
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
PART 2
PRODUCTS
2.1
EQUIPMENT AND COMPONENTS
Equipment and components shall conform to applicable requirements of NFPA 70.
Units of the same type of the equipment shall be product of single
manufacturer. Units to be mounted outside or subject to inclement
conditions shall be weatherproof or to be mounted in weatherproof
enclosures.
[2.1.1
Type 1 System:
Direct Connected Keyed Intercommunication System
**************************************************************************
NOTE: Select the appropriate paragraph and its
following subparagraphs for the features desired.
Delete all paragraphs describing unwanted features.
**************************************************************************
Provide master stations and remote stations in the quantities indicated.
Each master station shall selectively communicate with any other master
station and any remote station by actuating an appropriate selector switch.
[Each master station shall be capable of initiating a message to all other
master stations and all remote stations simultaneously or in groups of not
less than ten stations per group.]
2.1.1.1
Master Station
[Desk] [surface wall] [recessed wall] [rack]-mounted master stations shall
as a minimum conform to the following specifications:
a.
Capacity:
Accommodate [_____] stations
SECTION 16822N
Page 8