3.8.4
UPS
Provide an UPS for all equipment that operates directly off of ac line
and a monitor, the UPS shall be used to power both the computer and monitor.
3.8.5
Software
a. Provide all software programs as required for all specified
capabilities and performance, and pertinent software manuals. Include all
operating systems, application programs, and a complete set of backup
software.
b. Provide Call Logging application software for installation on the
medical center Information System terminals and computers.
3.8.6
Cord Sets and Wall Brackets
a. Furnish one (1) pillow speaker cord set for each patient station that
is located in a patient bedroom equipped with a patient TV Set.
b. Furnish one (1) push button cord set for each patient station that is
located in a patient care room which in not equipped with a patient TV Set.
c.
Furnish pneumatic cord sets for 25% of all patient stations.
d.
Provide one (1) cord set wall bracket for each patient station.
3.8.7
LAN
Provide all system LAN hardware, software and cabling as required by the
system Manufacturer and the system application design. Install all LAN
hardware in telecommunications rooms.
3.8.8
Servers
a. Provide and interconnect all servers as required by system application
design.
b. The telecommunication drawings indicate space in telecommunications
rooms that has been designated for the installation of system equipment.
As required by the system application design, furnish and install the type
and quantity of servers in these designated locations.
3.8.9
Pagers
Provide [Qty.] [Make], [Model] alphanumeric text pagers.
Furnish the
pagers to the Contracting Officer.
3.8.10
Product Samples
**************************************************************************
NOTE: If the Design Agency or Using Service
requests samples, include this paragraph.
**************************************************************************
Provide one sample unit of each type of station, light, and cord set for
approval as part of the Samples submittal.
SECTION 16731A