output within 3 minutes after primary or emergency
power is applied.
Incandescent lamps may be used to provide required
light output during periods of restart.
**************************************************************************
2.16.1
High-Pressure Sodium
Lamps shall conform to NEMA C78.42. Ballasts shall conform to ANSI C82.4,
or UL 1029. High-pressure sodium lamps shall be clear.
2.16.2
Mercury Vapor
**************************************************************************
NOTE: To save energy, mercury vapor fixtures shall
only be used when matching existing fixtures.
**************************************************************************
Lamps shall conform to ANSI C78.40.
Ballasts shall conform to ANSI C82.4.
2.16.3
Metal-Halide
Lamps shall be made by a manufacturer with not less than 5 years experience
in making metal-halide lamps. Metal-halide lamps shall conform to ANSI
C78.1375 or ANSI C78.1376. Ballasts shall conform to ANSI C82.4 or UL 1029.
2.17
LAMPS, INCANDESCENT
Incandescent lamps shall conform to UL 1598 and shall be rated for 12O volt
operation unless otherwise specified.
2.18
LAMPS, FLUORESCENT
Fluorescent lamps shall have standard cool-white color characteristics and
shall not require starter switches. The lamps shall be of the rapid-start
type.
2.19
LUMINAIRE COMPONENTS
Luminaire components shall conform to the following: attachments, NEMA
NEMA C136.15; interchangeability, NEMA C136.6 and ANSI C136.9; and sockets,
ANSI C136.11.
2.20
LIGHTING CONTROL EQUIPMENT
2.20.1
Photo-Control Devices
**************************************************************************
NOTE: If automatic control of luminaires is
desired, first consideration shall be given to
photo-control. If both photo-control and remote
manual override are required for the lighting
system, a central contactor and a single system
photo-cell shall be used. Individual luminaire
be used where a remote manual override is required.
**************************************************************************
SECTION 16528A
Page 25