Automatic Transfer Switch Drawings; G
SD-03 Product Data
Automatic Transfer Switches; G
SD-06 Test Reports
Acceptance Checks and Tests; G
Functional Acceptance Tests; G
SD-07 Certificates
Proof of Listing; G
SD-10 Operation and Maintenance Data
Automatic Transfer Switches, Data Package 5; G
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
1.4
QUALITY ASSURANCE
1.4.1
Proof of Listing
Submit proof of listing by UL 1008.
1.4.2
Automatic Transfer Switch Drawings
drawings shall include manufacturer's name and catalog number, electrical
ratings, total system transfer statement, reduced normal supply voltage at
which transfer to the alternate supply is initiated, transfer delay times,
terminals, tightening torque for each wire connector, and other required UL
1008 markings.
PART 2
PRODUCTS
2.1
AUTOMATIC TRANSFER SWITCHES
**************************************************************************
NOTE: Select the following options for switches to
be installed in facilities complying with
MIL-HDBK-1191, DOD Medical and Dental Treatment
Facilities Design and Construction Guide: (a)
acceptable"; (b) "Automatic Transfer Switches
provided with a by-pass/isolation switch shall be
mounted on a drawout mechanism so that the automatic
transfer switch can be removed from the enclosure".
**************************************************************************
in accordance with UL 1008. Each automatic transfer switch shall be rated
SECTION 16410N