IEEE C62.11 and shall be provided where indicated. Arresters shall be
[station] [intermediate] [distribution] class, rated as shown. Arresters
for use at elevations in excess of 1.8 km 6000 feet above mean sea level
shall be specifically rated for that purpose. Arresters shall be equipped
with mounting brackets suitable for the indicated installations. Arresters
shall be of the [valve] [or] [metal-oxide varistor] [or] [combination
valve-metal-oxide varistor] type.
2.12
2.12.1
Driven Ground Rods
Ground rods shall be [copper-clad steel conforming to UL 467] [zinc-coated
steel conforming to ANSI C135.30] [solid stainless steel] not less than [
15.9 mm 5/8 inch] [19 mm 3/4 inch] in diameter by [3.1 m 10 feet] [2.44 m 8
feet] in length. Sectional type rods may be used.
2.12.2
Grounding Conductors
Grounding conductors shall be bare, except where installed in conduit with
associated phase conductors. Insulated conductors shall be of the same
material as phase conductors and green color-coded, except that conductors
shall be rated no more than 600 volts. Bare conductors shall be ASTM B 8
soft-drawn unless otherwise indicated. Aluminum is not acceptable.
2.13
CONCRETE AND REINFORCEMENT
Concrete work shall have minimum 20 MPa 3000 psi compressive strength and
conform to the requirements of Section 03300A CAST-IN-PLACE STRUCTURAL
CONCRETE. Concrete reinforcing shall be as specified in Section 03200A
CONCRETE REINFORCEMENT.
2.14
PADLOCKS
Padlocks shall comply with Section 08710 DOOR HARDWARE.
2.15
CABLE FIREPROOFING SYSTEMS
Cable fireproofing systems shall be listed in FM P7825a as a
and shall be suitable for application on the type of medium-voltage cables
provided. After being fully cured, materials shall be suitable for use
where exposed to oil, water, gases, salt water, sewage, and fungus and
shall not damage cable jackets or insulation. Asbestos materials are not
acceptable.
2.15.1
Fireproof Coating
Cable fireproofing coatings shall be compounded of water-based
thermoplastic resins, flame-retardant chemicals, and inorganic
noncombustible fibers and shall be suitable for the application methods
used. Coatings applied on bundled cables shall have a derating factor of
after curing.
2.15.2
Fireproofing Tape
Fireproofing tape shall be at least 50 mm 2 inches wide and shall be a
flexible, conformable, polymeric, elastomer tape designed specifically for