2.2
Insulated High-Voltage Connectors
IEEE Std 386. Provide corresponding connector for each switched way.
Connectors shall have a steel reinforced hook-stick eye, grounding eye,
test point, and arc-quenching contact material.
[a.
200 Ampere loadbreak connector ratings: Voltage: [15 kV, 95 kV
BIL][25 kV, 125 kV BIL][35 kV, 150 kV BIL]. Short time rating:
10,000 rms symmetrical amperes.]
**************************************************************************
NOTE: For LANTDIV projects, provide 200 ampere
bushing interface on all 600 ampere connectors.
**************************************************************************
[b.
600 Ampere deadbreak connector ratings: Voltage: [15 kV, 95 kV
BIL][25 kV, 125 kV BIL][35 kV, 150 kV BIL]. Short time rating:
40,000 rms symmetrical amperes.[ Connectors shall have 200 ampere
bushing interface[ for surge arresters][ as indicated].]]
**************************************************************************
NOTE: Include the following paragraph only when the
activity requires additional grounding elbows and
feed-thru inserts.
**************************************************************************
[c.
Provide[ [one][____] set[s] of three grounding elbows][ and][
[one][____] set[s] of three feed-thru inserts]. [Grounding
elbows][ and ][feed-thru inserts] shall be delivered to the
Contracting Officer.]
[2.3
Surge Arresters
IEEE C62.11, rated[[ 3][ 6][ 9][ 10][ 12][ 15][_____] kV][ as indicated],
fully shielded, dead-front, metal-oxide-varistor, elbow type with
resistance-graded gap, suitable for plugging into inserts. Provide
arresters on switched ways as indicated.
][2.4
SF6 Refill Cylinders
**************************************************************************
NOTE: Include the following paragraph only when the
activity requires additional SF6 refill cylinders.
**************************************************************************
Provide [two][____] SF6 refill cylinders, minimum size of 6 pounds of SF6;
include regulator, valves, and hose for connection to the fill valve of the
switch.
]2.5
SOURCE QUALITY CONTROL
2.5.1
Switchgear Design and Production Tests
**************************************************************************
NOTE: Include IEEE C37.60 when the switchgear will
have fault interrupting switched ways.
**************************************************************************
**************************************************************************
SECTION 16341N
Page 11