TABLE 2
Bench Test Measurements
125 V, 100 dB at 14 kHz
MIL-STD-220A + /\
Current Rating
Attenuation
(Amps)
at 14 kHz (dB)
2.5
+6
5
+0
10
-6
20
-12
25
-14
30
-16
50
-20
60
-22
75
-24
100
-26
150
-30
200
-32
300
-36
400
-38
500
-40
600
-42
1000
-44
277 V, 100 dB at 14 kHz
Current Rating (Amps)
30
-9
60
-15
100
-19
250
-27
500
-34