[_____]] with individual power line filters mounted and access cover plate
attached.
2.4
FILTER CONNECTIONS
**************************************************************************
NOTE: When installation of the filter unit inside
of the shielded enclosure is required, the power
input terminal compartment shall be RF tight instead
of the load terminal compartment; and the filters
shall be located in the load terminal compartment.
This arrangement is necessary to prevent radiated RF
energy within the shielded enclosure from inducing
RF energy in the power conductors between the
filters and the point where the conductors pass
through the shielded enclosure wall. To provide for
this arrangement, change the wording as necessary,
i.e., change the word "Load" to read "Power Input"
and change the words "Power Input" to read "Power
Output" or "Load," as appropriate.
**************************************************************************
**************************************************************************
NOTE: If no drawings are furnished with the
specifications, specify the wire size.
**************************************************************************
Equip individual filters within a unit with insulated terminals and
incorporate suitably sized flexible leads from insulated filter terminals
to standoff insulator terminals or insulated terminal blocks. Mount
standoff insulator terminals or insulated terminal blocks in terminal
compartments. Provide solderless lugs for connecting phase and neutral
wires to filter units. Lugs shall be hex head bolt or screw type and shall
conform to UL 486A-486B. Space live parts in accordance with UL 1283.
Filter leads shall be copper.
2.5
INDIVIDUAL FILTERS
2.5.1
Filter Construction
After filter is filled with an impregnating or encapsulating compound, weld
seams. When solid potting compound is used to fill filter, filters may be
mechanically secured and sealed with solder. Use hermetically sealed
impregnated capacitors, or vacuum impregnate complete filter assembly.
Fabricate individual filter cases from not less than number 16-gage steel
and finish cases with a corrosion-resistant plating.
2.5.2
Impregnating or Potting Compound
Fill filter with an impregnating or potting compound meeting requirements
of MIL-F-15733 and having a flashpoint for operating temperature range B as
defined in Table VIII of MIL-F-15733.
2.5.3
Overload Requirements
Provide as specified in MIL-F-15733.
SECTION 16280N
Page 10