condition are in accordance with the contract specification.
Manufacturer's statements shall certify provision of features which cannot
be verified visually.
1.
2.
Governor type and features. (I)
3.
Engine timing mark. (I)
4.
Starting motor. (I)
5.
Starting aids. (I)
6.
Coolant type and concentration. (D)
7.
Radiator drains. (I)
8.
Block coolant drains. (I)
9.
Coolant fill level. (I)
10.
Coolant line connections. (I)
11.
Coolant hoses. (I)
12.
13.
Intake air silencer. (I)
14.
Lube oil type. (D)
15.
Lube oil drain. (I)
16.
Lube-oil filter. (I)
17.
Lube-oil-fill level. (I)
18.
Lube-oil line connections. (I)
19.
Lube-oil lines. (I)
20.
Fuel type. (D)
21.
Fuel-level. (I)
22.
Fuel-line connections. (I)
23.
Fuel lines. (I)
24.
25.
Access for maintenance. (I)
26.
Voltage regulator. (I)
27.
Battery-charger connections. (I)
28.
Wiring & terminations. (I)
29.
30.
Hazards to personnel. (I)
31.
Base. (I)
32.
Nameplates. (I)
33.
Paint. (I)
34.
35.
Access provided to controls. (I)
36.
Enclosure. (I)
37.
Engine & generator mounting bolts (proper application). (I)
3.5.4
Safety Run Tests
**************************************************************************
NOTE: For the sound level tests, modify the radial
distance requirement from the engine intake and
exhaust to account for obstructions, variations in
site conditions, building configurations; or
indicate points on the contract drawings at which
measurements are to be made.
Delete item w if a day tank is not used.
Add the following test under item x below when
Coordinate the requirement with paragraph Alarm
Panels.