attached to a seismic-resistant ceiling support system built in accordance
with [ASTM E 580] [Section 09510 ACOUSTICAL CEILINGS]. Seismic protection
for the fixtures shall conform to the requirements of TI 809-04, Chapter 10.
3.2.3
Assembly Mounted on Outlet Box
A supporting assembly, that is intended to be mounted on an outlet box,
shall be designed to accommodate mounting features on [100] [75] mm [4] [3]
inch boxes, plaster rings, and fixture studs.
3.2.4
Wall-Mounted Emergency Light Unit
Attachments for wall-mounted emergency light units shall be designed and
secured for the worst expected seismic disturbance at the site.
3.2.5
Lateral Force
Structural requirements for light fixture bracing shall be in accordance
with Section 13080 SEISMIC PROTECTION FOR MISCELLANIOUS EQUIPMENT.
-- End of Section --