shall include equipment to protect the lime from moisture. Slakers shall
discharge slurry by gravity flow into product tank. Slurry preparation
system shall include positive means of removing sufficient grit from the
slurry to assure proper operation of the slurry feed system and the spray
atomizers. Grit shall be conveyed to a disposal bin provided by the
Government. Provide emergency eyewash stations at each level in the lime
slurry preparation system enclosure. Provide piping to exterior of
enclosure for connection to potable water piping system provided by the
Contractor.
2.6.5
Ductwork
**************************************************************************
NOTE: Ductwork velocities shall be such to maintain
self-cleaning conditions.
**************************************************************************
Ductwork upstream of the fabric filter baghouse outlets shall be designed
for a velocity of [_____] meter per second feet per minute at the design
flue gas flow, specified in paragraph entitled "Expected Flue Gas
Conditions." Ductwork downstream of the fabric filter baghouse outlets
shall be designed for a velocity of [_____] m/s fpm at the design flue gas
flow, specified in paragraph entitled "Expected Flue Gas Conditions."
Ductwork from the fabric filter baghouse outlet to the stack inlet shall be
designed to withstand a transient internal pressure (80 percent of yield
strength) range of minus 2490 Pa to plus 7470 Pa 10 inches Water Column
(WC) to plus 30 inches WC without permanent deformation of any structural
member at yield or in buckling.
2.6.6
Induced Draft Fans
**************************************************************************
NOTE: Pressures and air flows will be site specific
and will require system analysis.
**************************************************************************
**************************************************************************
NOTE: Dry and Wet Bulb Temperature and Duration:
Temperature
Parameter
Season
(Degrees C)
of Higher Temperatures
Dry Bulb
Dec.-Feb.
[______]
[______]
Dry Bulb and
June-Sept.
[______]
[______]
Mean Coincident
Wet Bulb
Wet Bulb
June-Sept.
[______]
[______]
Temperature
Parameter
Season
(Degrees F)
of Higher Temperatures
Dry Bulb
Dec.-Feb.
[______]
[______]
Dry Bulb and
June-Sept.
[______]
[______]
Mean Coincident
Wet Bulb
SECTION 15864N
Page 35