secondary for connection to the [boiler] [incinerator] local
hopper heater control panel. Provide thermostats with a set point
range of 38 to 260 degrees C 100 to 500 degrees F. Thermostats
shall measure hopper skin temperature using ungrounded, Type J
thermocouples. The local hopper heater control panel cover shall
contain the following devices.
(1)
"START UP," "ON LINE," "OFF," "AUTO" selector switch.
(2)
(3)
120 V "LO TEMP" alarm white light with integral transformer.
(4)
Device and enclosure nameplates.
Wire the selector switch for the following system operation:
(1)
"START UP":
All elements on (includes throat heater).
(2)
"ON LINE":
All elements on (includes throat heater).
(3)
"OFF":
All elements off.
(4) "AUTO": Control functions transfer to Master Hopper Heater
Control Panel.
c.
Master Hopper Heater Control Panel: Provide panel(s) containing
other devices required for complete control of [each] hopper
the control room. Panel components shall be factory installed and
wired in a NEMA ICS 6, type 4 enclosure and shall include the
following:
(1)
A main circuit breaker.
open contacts. The contactor shall have a 120-volt operating coil.
(3)
"START UP," "ON LINE," "OFF," selector switch for each hopper.
(4) 120 V red "ON" light and 120 V white "LO TEMP" alarm light
(5) Auxiliary relays and equipment required for operation of the
(6)
Device and enclosure nameplates.
(7)
Fused control transformer having a 120 volt AC secondary.
2.2.5
Fly Ash Level Alarms
**************************************************************************
NOTE: The nuclear detector radiation should not
exceed 6x10-7 sievert per hour 0.06 mR/Hr. The
designer must contact the safety department of the
using activity to coordinate the limit of the
SECTION 15861N
Page 26