shall be connected by brass pipe and fittings with shutoff cocks. Where
placed close to the pressure reducing assembly, but connected approximately
3 m 10 feettherefrom. Operating ranges of the gauges shall be
2.9.17.1
Pressure Gauges (Panel)
[Three] [_____] 150 mm 6 inch dial size, phenol or brass, black enamel
finished case, gauges shall be furnished and installed to indicate main
steam, boiler feedwater, and deaerator makeup. Gauges shall be Bourdon
tube style with back connections and white dials with black lettering.
Steam gauges shall be equipped with siphons and all gauges shall have
shutoff valves at the panel. Panel entry shall be through bulk-head
connectors located in the upper part of the panel. Gauge accuracy shall be
at least 1/2 of 1 percent and normal readings shall be approximately 50 to
75 percent of full scale reading. The gauges shall be labeled:
Tag Number
Service
Pressure Range, kPa
PI-[_____]
Condensate, Supply Pressure
-69 to 345
PI-[_____]
Feedwater, Supply Pressure
0 to 2068
PI-[_____]
Main Steam, Steam Pressure
0 to 2068
Tag Number
Service
Pressure Range (psig)
PI-[_____]
Condensate, Supply Pressure
-10 to 50
PI-[_____]
Feedwater, Supply Pressure
0 to 300
PI-[_____]
Main Steam, Steam Pressure
0 to 300
2.9.17.2
Pressure Gauges (Local)
[_____] 115 mm 4-1/2 inch dial size, phenol or brass, black enamel finished
case, gauges shall be furnished and installed for the services shown below.
Gauges shall be Bourdon-tube style with bottom connections and white dials
with black lettering. Steam gauges shall be equipped with siphons and all
shall be installed with shutoff valves. Gauge accuracy shall be at least
1/2 of 1 percent and normal readings shall be approximately 50 to 75
percent of full scale reading.
Tag Number
Service
PI-[_____]
Condensate Pump Number 1, Discharge Pressure.
PI-[_____]
Condensate Pump Number 2, Discharge Pressure.
PI-[_____]
PI-[_____]
B.F. Pump Number 1, Suction Pressure.
PI-[_____]
B.F. Pump Number 1, Discharge Pressure.
PI-[_____]
B.F. Pump Number 2, Suction Pressure.
PI-[_____]
B.F. Pump Number 2, Discharge Pressure.
SECTION 15846A
Page 56