2.1.3.4
Boiler Operating Capacity
The boiler shall maintain continuous capacity within the specified range
while operating on [1] [2] [3] shifts per day, [_____] days per week
schedule at the specified pressure with boiler feedwater at a temperature
of approximately [_____] degrees C degrees F. The hot gas entrance
temperature shall be [_____] degrees C degrees F and the flue gas outlet
temperature shall be [_____] degrees C degrees F, based on a flow of
[_____] actual cubic meters/second ACFM. Moisture in the steam and boiler
water concentrations shall be in accordance with ABMA Boiler 400.
2.1.3.5
Boiler Output Capacity
Output capacity of the boilers shall be based on tests of the boilers and
combustion equipment as a unit. Efficiency shall be a minimum of [80]
[_____] percent at maximum continuous capacity.
2.1.3.6
Boiler Markings
**************************************************************************
NOTE: Delete brackets if the boiler does not
include a superheater.
**************************************************************************
Each boiler shall also be furnished with a metal nameplate which shall
include the following information:
a.
Maximum continuous capacity in Watts and Btu per hour Btu/hour.
b.
Radiant heating surface in square meters square feet.
c.
Total heating surface in square meters square feet.
d.
Boiler maximum allowable working pressure.
e.
Boiler system ASME Code Stamp and Certification.
f.
Maximum steam flow of boiler in kg/hour pounds/hour.
g.
Manufacturer's Model Number.
h.
Serial Number.
i.
Year manufactured.
j.
[Superheater final steam temperature in degrees C degrees F.]
k.
[Superheater heating surface in square meters square feet.]
2.1.3.7
Noise
**************************************************************************
NOTE: Indicate the noise level required by the
location of the equipment. Equipment in remote
areas can be allowed to produce noise at a level
slightly higher than the normal 85 decibel-A scale
(dBA). Occupational Safety and Health
Administration (OSHA) regulations and Corps of
SECTION 15846A
Page 20