corrosion inhibitors are not contained in freeze protection solution in the
ground heat exchanger loop.
2.10.3
Ground Heat Exchanger Piping
Provide corrosion inhibitors acceptable to heat pump manufacturers with
concentrations suitable for each system[ and appropriate for the antifreeze
used].
PART 3
EXECUTION
3.1
INSTALLATION
3.1.1
Heat Pump System
Maintenance access to each piece of equipment shall not be compromised by
any type of piping, electrical conduit, or any other utility. Further,
install equipment in accordance with the manufacturer's written
installation instructions, including the following:
]
[Closed Circuit Coolers - installation instructions]
[Heat Tape - installation instructions]
3.1.2
Connections to Existing Systems
Notify the Contracting Officer in writing at least 15 calendar days prior
to the date the connections are required. Obtain approval before
interrupting service. Furnish materials required to make connections into
existing systems and perform excavating, backfilling, compacting, and other
incidental labor as required. Furnish labor and tools for making actual
connections to existing systems. Flush existing systems in accordance with
paragraph entitled "Flushing the Ground Heat Exchanger" prior to making
connections.
3.2
ABOVEGROUND PIPING
Provide unions in piping to facilitate removal of heat pump for maintenance
or replacement. Test, inspect, and approve piping before covering or
concealing. Provide fittings for changes in direction of piping and for
connections. Make changes in piping sizes through tapered reducing
fittings; bushings will not be permitted. Install valves with stems
horizontal or above. Provide flanges or unions at valves, traps,
strainers, and connections to equipment; unions are not required in copper
a.
Threaded Connections: Threaded joints shall be sealed with a
sealant compatible with the circulating fluid; use of Teflon tape
is not permitted. Do not thread metal pipe into plastic piping.
b.
Pipe Hangers and Supports: Install in accordance with MSS SP-69.
Provide additional pipe hangers and supports at in-line water
SECTION 15741N
Page 30