enter and leave fans axially. Streamline inlet with conversion vanes [and
bell-mouth]. Enclose and isolate fan bearings and drive shafts from air
stream. [Furnish direct-drive TEAC motors.] [Guard V-belt drives of
drip-proof motors mounted out of air stream.] Provide fan supports [and
2.1.6
Air-Circulating Fans
**************************************************************************
NOTE: These fans are not allowed when local exhaust
system is used in the room or space.
**************************************************************************
UL 507 and UL listed, propeller ceiling type, with size and electrical
characteristics as indicated.
2.1.7
Air Curtains
AMCA 210 and AMCA 220 with AMCA seal, factory-fabricated, [insect]
[thermal] control type, angle adjustment feature, minimum air velocity [3]
[8] meter per second (m/s) [600] [1,600] feet per minute (fpm), measured at
points one meter 3 feet above the floor, and minimum air capacities and
electrical characteristics.
2.2
CENTRAL STATION AIR HANDLERS
**************************************************************************
NOTE: ARI 210, 240, or 360, unitary air
conditioning equipment with direct expansion coil
are covered by Section 15730, "Unitary Air
Conditioning Equipment." Fan-coil units are covered
in ARI 440. For other exclusions, see ARI 430. In
the industry, the provision of heating and cooling
sections may be added by being rated separately,
with coils per ARI 410, electric heaters per UL
1096, or gas-fired heaters per AGA Z21.47.
**************************************************************************
**************************************************************************
NOTE: Indicate sound ratings or loudness level of
equipment in the Equipment Schedule on the drawings.
**************************************************************************
ARI 430 with sound rating in accordance with ASHRAE 68, [[single-] [multi-]
zone] [or] [double-deck] type, sound power level, and static pressure, as
indicated. Include damper section, supply blower section, filter section
with mixing box section or combination filter-mixing box section, and
[coil] [or] [heater] section. Filters, housing coils, and heaters must be
completely removable from the unit without having to dismantle the unit or
adjacent equipment.
2.2.1
Casings
Construct casings of steel, galvanized steel, or aluminum on channel base
[and drain pan] coated externally with manufacturers standard paint finish.
Provide removable panels and access doors for inspection and access to
internal parts. Insulate casings with manufacturer's standard materials.
For outdoor roof mounted units, provide weatherproof casing in accordance
with paragraph entitled "Testing for Corrosion Protection." Finish with
SECTION 15720N
Page 12