other cold pour joints. Basin wall sections shall be made in a second
continuous pour, contain the necessary reinforcing steel as submitted by
the manufacturer and approved, and be arranged to interlock with the
water-stop seal in the floor slab, forming a completely waterproof basin.]
2.5.13
Electric Basin Heater
Heater shall be the electric immersion type with water-tight junction boxes
mounted in the basin with sufficient capacity to maintain the basin water
temperature above 4.4 degrees C 40 degrees F at an ambient temperature of
[_____] degrees C degrees F. Heater shall be complete with control
thermostat, transformer, contactor, and low water level heater protection.
2.5.14
Hot Water Distribution System
**************************************************************************
NOTE: The gravity-flow type distribution system
will be the system of choice. Pressurized-flow type
systems will typically only be specified for
field-erected, counterflow type towers
Piping connecting to a cooling tower will be
externally supported, independent of the tower
structure and piping.
**************************************************************************
Water distribution shall be the [gravity-flow] [pressurized-flow] type
system which distributes waters evenly over the entire fill surface. Each
tower cell shall be designed so that a water flow of 140 percent capacity
will not cause overflowing or splashing. The distribution system for each
system shall be self-draining and nonclogging. Piping shall be either cast
iron, ductile iron, threaded-glass-fiber reinforced epoxy pipe,
polypropylene, PVC or Schedule 80 black steel.
2.5.14.1
Gravity-Flow System
System shall be provided with open basins which include a splash box or
baffles to minimize splashing of incoming hot water and holes that evenly
distribute the water over the entire decking area. Holes used in a water
basin shall be provided with ceramic or plastic orifice inserts.
2.5.14.2
Pressurized-Flow System
System shall include piping, fittings, branches, and spray nozzles. Spray
nozzles shall be stainless steel, bronze, polypropylene, or high-impact
plastic. Nozzles shall be cleanable, nonclogging, removable, and spaced
for even distribution.
2.5.14.3
Basin Cover
Hot water distribution basins shall be provided with the tower
manufacturer's standard removable, [wood] [zinc-coated steel] [stainless
steel] [FRP] covers. Covers shall prevent airborne debris from entering
the basin.
2.5.15
Drift Eliminators
**************************************************************************
SECTION 15645A