2.6.4.7
Energy Management Control System (EMCS) Interface
The control system shall be capable of communicating all data to a remote
integrated DDC processor through a single shielded cable. The data shall
and safety shutdown conditions. The control system shall also be capable
of receiving at a minimum the following operating commands.
a.
Remote Unit Start/Stop
b.
[Remote Chilled Water Reset]
c.
2.6.5
Compressor(s)
2.6.5.1
Reciprocating Compressor(s)
Rotating parts shall be statically and dynamically balanced at the factory
to minimize vibration. Compressors shall be capable of operating at
partial-load conditions without increased vibration over the normal
vibration at full load operation and shall be capable of continuous
operation down to the lowest step of unloading as specified. Compressors
of size 7.45 kW 10 horsepower and above shall have an oil lubrication
system of the reversible, forced-feed type with oil strainer. Shaft seal
in open-type units shall be mechanical type. Piston speed for open-type
compressors shall not exceed the manufacturer's recommendation or 6 m/s
1200 fpm, whichever is less. Compressors shall include:
a.
Vertical, V, W, or radial cylinder design
b.
Oil lubrication
c.
Integrally cast block of close-grained iron or cast aluminum block
with hardened steel cylinder sleeves
d.
Oil-level bull's eye
e.
Cast cylinder heads
f.
Cast-aluminum or forged-steel connecting rods
g.
h.
i.
Crankcase oil heaters controlled as recommended by the manufacturer
j.
Suction and discharge refrigerant service valves that are flange
connected, wrench operated, with cap
k.
A strainer on the suction side of the compressor
l.
[A hot-gas muffler to reduce vibration and noise from pulsations]
2.6.5.2
Scroll Compressor(s)
Compressors shall be of the hermetically sealed design. Compressors shall
be mounted on vibration isolators to minimize vibration and noise.