which the equipment will be subjected. Coordinate
this temperature with manufacturers to assure
available equipment.
A cooling tower bypass line and modulating control
valve should be evaluated and incorporated into a
design which requires chiller operation in ambient
temperatures less than 13 degrees C (55 degree F).
**************************************************************************
Chiller shall be provided with the following adjustable operating controls
as a minimum.
a.
Leaving chilled water temperature control
b.
Adjustable timer or automated controls to prevent a compressor
from short cycling
c.
d.
Load limiting
e.
with the system load and the programmable setpoints. Controls
shall automatically re-cycle the chiller on power interruption.
f.
all ambient temperatures down to [_____] degrees C F
g.
2.6.4.2
Monitoring Capabilities
display shall not require opening or removing any panels or doors.
a.
Entering and leaving chilled water temperatures
b.
Self diagnostic
c.
Operation status
d.
Operating hours
e.
Number of starts
f.
Compressor status (on or off)
g.
Refrigerant discharge and suction pressures
h.
Oil pressure
i.
[Condenser water entering and leaving temperatures]
j.
[Number of purge cycles over the last 7 days]
SECTION 15620A
Page 25