multicompressor units, not less than two independent refrigerant circuits
shall be provided. Chillers shall operate at partial load conditions
without increased vibration over normal vibration at full load, and shall
be capable of continuous operation down to minimum capacity. Provide
insulation for surfaces subject to sweating including the liquid cooler,
suction line piping, water boxes, economizer, and cooling lines. Insulation
shall conform to Section 15080 THERMAL INSULATION FOR MECHANICAL SYSTEMS.
2.2.1
Reciprocating Compressors
Provide with forced feed lubrication, crankcase heater, hot-gas muffler,
and suction strainer. Cylinder-unloading devices shall be unloaded when
compressor starts. Piston speed for open compressor shall not exceed
recommendations of manufacturer or 5 m/s 1000 fpm, whichever is less.
2.2.2
Helical Rotary Compressors
Positive displacement, oil-injected type, and driven by an electric motor.
Rotors shall be solid steel, Society of Automotive Engineers Grade 1141 or
1144. Shaft main bearings shall be either sleeve-design type with leaded
bronze or steel-backed babbit; or frictionless bearing design, ball or
roller type. Housings and covers shall be high-grade, cast-iron or
aluminum pressure castings. Lubrication system shall lubricate rotors,
bearings, shaft seal as well as rotor sealing and cooling. Provide an oil
safety cutout interlocked with the compressor starter to allow compressor
to operate only when the oil system is operational. Provide for
lubrication of bearings and shaft seals on shutdown with or without
2.2.3
Scroll Compressors
Three-dimensional, compliant, hermetically sealed design. Compressors
shall be mounted on vibration isolators. Rotating parts shall be factory
balanced. Main bearings shall be rolling-element type. Lubrication
systems shall be centrifugal pump type including oil level sight glass and
oil charging valve.
2.2.4
Tubes shall be seamless copper. On direct-expansion-type units, each
refrigerant circuit shall be complete with liquid solenoid valve and
expansion device capable of modulating to minimum capacity. For the water
side of liquid cooler, performance shall be based on a water velocity not
less than 0.91 m/s 3 fps and not more than 3.66 m/s 12 fpsand a fouling
factor of 0.00025.
2.2.5
Controls, Control Panels, and Gages
**************************************************************************
NOTE: Specify required time delay for type and size
of unit after consulting current literature.
**************************************************************************
**************************************************************************
NOTE: Specify lowest percent of full capacity
required. Check for availability before inserting
number in blank.
**************************************************************************