12-volt signal to water meter, and pulse accumulator.
2.11.4
Deaerator Condensate Return System Chemical Treatment System
**************************************************************************
NOTE: Select 200 liter (50 gallon) drum for boiler
plant up to 22,650 kg/hr
**************************************************************************
One feedwater chemical treatment system for deaerator shall be provided
including the following:
a.
One chemical feed pump. Chemical feed pump shall be provided with
pressure relief valve piped on discharge side of chemical feed
pump to divert overpressurized chemical solution back to the
storage tank. Chemical feed pump shall have capability of
accepting 4 to 20 mA dc signal.
b.
[One 8000 liter 200 gallon tank.]
OR
c.
[One 200 liter 50 gallon tank.]
e.
One contacting head water meter shall be provided. Maximum
temperature shall be 120 degrees C 250 degrees F. Meter shall be
f.
Proportional chemical feed controller and electronic pulse timer.
Electronic pulse timer shall control proportional feed of
treatment chemicals based on makeup water as measured by
contacting head water meter. Controller shall have following
features:
(1)
Painted steel NEMA 12 enclosure
(2) Panel display including one proportional pulse timer,
Automatic-Off-Manual switch. Test momentary switch which
simulates a water meter pulse and runs timer for one cycle, and
pulse accumulator.
2.11.5
Testing Equipment
Testing equipment, including carrying case and spare reagent, for
maintaining control of a program of water treatment standards in steam
boiler system shall be provided in accordance with the water treatment plan.
Testing equipment shall consist of the following:
a.
Reagents and apparatus for determination of phosphate and sulfite
levels in the boiler water.
b.
Reagents and apparatus for determination of PH, P and M alkalinity
and chloride.
c.
Reagents and apparatus for determination of neutralizing amine
level in the steam and condensate return lines.
d.
One conductivity meter with temperature compensation and multiple
SECTION 15561A
Page 91