the top grate line and the first plane of entry into, or between the tubes,
of the furnace face of the bridge wall. When screen or superheater tubes
are utilized, they shall be considered as the first plane of entry. The
manufacturer shall state the furnace volume of the boiler.
1.3.5
PVC
Poly-vinyl chloride.
1.3.6
Standard Commercial Product
Standard commercial product is a product which has been sold or is being
currently offered for sale on the commercial market through advertisements
or manufacturer's catalogs, or brochures, and represents the latest
production model.
1.3.7
System Supplier
A manufacturer, fabricator, erector, corporation or firm that regularly is
employed in the design, fabrication, erection (or erection supervision),
testing and startup of systems comparable in size and type to those
specified and indicated. System supplier shall arrange the equipment
supervise erection, and startup and test the equipment.
1.4
SYSTEM DESCRIPTION
1.4.1
1.4.1.1
Boiler
Design boiler in accordance with the ASME BPVC SEC I. Provide design data
with computations and performance guarantees covering the full range of
operation at full load, 75 percent load, 50 percent load and 30 percent
load. Assemble tubes, drums, and headers so that the entire boiler can be
drained dry. The furnace shall be water cooled on the side, top, front and
back walls.
a.
Boiler design and service conditions
(1) Steam capacity:
Continuous peak for 2 hours: [_____] kg/sec lb/hr
Maximum continuous: [_____] kg/sec lb/hr
Minimum (without smoking): [_____] kg/sec lb/hr
(2)
Design pressure:
[_____] kPa (gage) psig
(3)
[_____] kPa (gage) psig
(4)
Steam temperature:
[_____] degrees C F
(5) Feedwater temperature to economizer:
[_____] degrees C F
Continuous blowdown: [_____] percent
(6) Maximum moisture content of steam
leaving drum at peak rating: [_____] percent
(7)
Total solids concentration in drum:
[_____] PPM