per cycle at a flowing water pressure of 549 kPa 80 psi if a
metering device or fitting is used that limits the period of water
discharge such as a foot switch or fixture occupancy sensor. If a
metering device is not used, the flow shall be limited to 0.16
L/second 2.5 gpm at a flowing water pressure of 549 kPa 80 psi.
cc.
Item P3250. Lavatory with back, 609.6 x 508.0 mm 24 x 20 inches,
shall conform to ASME A112.19.2M. Fixture shall be equipped with
combination faucet, elevated gooseneck spout, wrist action
handles, drain stopper with chain stay, "P" trap, and angle or
straight stop valves. Flow shall be limited to 1 liter 0.25 gallon
per cycle at a flowing water pressure of 549 kPa 80 psi if a
metering device or fitting is used that limits the period of water
discharge such as a foot switch or fixture occupancy sensor. If a
metering device is not used, the flow shall be limited to 0.16
L/second 2.5 gpm at a flowing water pressure of 549 kPa 80 psi.
dd.
Item P3300. Lavatory with back, 508.0 x 609.6 mm 20 x 18 inches,
shall conform to ASME A112.19.2M. Fixture shall be equipped with
cold water faucet only. In lieu of hot water faucet, cock hole
blank shall be provided. Drain stopper with chain stay,
continuous waste for groups of two and three lavatories, "P" trap,
and angle or straight stop valve shall be provided. Flow shall be
limited to 1 liter 0.25 gallon per cycle at a flowing water
pressure of 549 kPa 80 psi if a metering device or fitting is used
that limits the period of water discharge such as a foot switch or
fixture occupancy sensor. If a metering device is not used, the
flow shall be limited to 0.16 L/second 2.5 gpm at a flowing water
pressure of 549 kPa 80 psi.
ee.
Item P3440. Lavatory, surgeons, vitreous china, 711.2 X 533.4 mm
28 x 21 inches nominal dimensions; with bowl 355.6 x 279.4 mm 14 x
11 inches; and with two integral instrument trays, 355.6 x 114.3
mm 14 x 4-1/2 inches, designed to permit draining into the bowl;
gooseneck supply with knee control mixing valve. Flow shall be
limited to 1 liter 0.25 gallon per cycle at a flowing water
pressure of 549 kPa 80 psi if a metering device or fitting is used
that limits the period of water discharge such as a foot switch or
fixture occupancy sensor. If a metering device is not used, the
flow shall be limited to 0.16 L/second 2.5 gpm at a flowing water
pressure of 549 kPa 80 psi.
ff.
Item P3450. Lavatory with back, 508.0 x 609.6 mm 20 x 18 inches,
shall conform to ASME A112.19.2M. Fixture shall be equipped with
combination faucet, elevated gooseneck spout, wrist action
handles, drain fitting with strainer, "P" trap, and angle or
straight stop valves. Flow shall be limited to 1 liter 0.25 gallon
per cycle at a flowing water pressure of 549 kPa 80 psi if a
metering device or fitting is used that limits the period of water
discharge such as a foot switch or fixture occupancy sensor. If a
metering device is not used, the flow shall be limited to 0.16
L/second 2.5 gpm at a flowing water pressure of 549 kPa 80 psi.
gg.
Item P3451. Lavatory, exam room, vitreous china, front overflow,
508.0 x 457.2 mm 20 x 18 inches, with soap depression, gooseneck
faucet, aerator, 101.6 mm 4 inch wrist handles; plus open drain
with perforated grid; and with necessary accessory fittings. Flow
shall be limited to 1 liter 0.25 gallon per cycle at a flowing
water pressure of 549 kPa 80 psi if a metering device or fitting
SECTION 15405A
Page 34