TABLE 2
MAXIMUM SPAN FOR PIPE HANGERS (mm)
Copper tube, Type K (Cu-K) and Type L (Cu-L); PVC Schedule 40 and 80 (PVC);
brass and stainless steel (SS)
Pipe Size
Cu-K and Brass
Cu-L
PVC
SS
(mm)
100
2740
2660
1900
3500
125
3040
2890
---
3800
150
3270
3200
2050
4190
TABLE 2
MAXIMUM SPAN FOR PIPE HANGERS (feet)
Copper tube, Type K (Cu-K) and Type L (Cu-L); PVC Schedule 40 and 80 (PVC);
brass and stainless steel (SS)
Pipe Size
Cu-K and Brass
Cu-L
PVC
SS
(inches)
1/2
3'-9"
3'-6"
3'-6"
5'-0"
3/4
4'-3"
4'-3"
3'-6"
5'-9"
1
5'-0"
4'-9"
4'-0"
6'-6"
1 1/2
5'-9"
5'-6"
4'-6"
7'-6"
2
6'-6"
6'-6"
4'-6"
8'-6"
2 1/2
7'-3"
7'-0"
---
9'-3"
3
7'-9"
7'-6"
5'-6"
10'-3"
3 1/2
8'-3"
8'-3"
---
11'-0"
4
9'-0"
8'-9"
6'-3"
11'-6"
5
10'-0"
9'-6"
---
12'-9"
6
10'-9"
10'-6"
6'-9"
13'-9"
3.1.1.4
Exposed Oxygen Piping
Install in wall-mounted sheet steel raceways and junction boxes.
3.1.1.5
Threaded Joints
Coat male threads of fittings used in shut off valves with TFE tape before
assembly.
**************************************************************************
NOTE: Brazed joints exhibit a melting temperature
in excess of 538 degrees C 1000 degrees F to retain
the integrity of the piping system in the event of
fire exposure.
**************************************************************************
3.1.1.6
preparation and joining procedures shall conform with CDA A4015 and NFPA 99.
Use BCuP Series brazing alloys for joints, except for 50 mm 2 inch and
smaller pipes, in nitrogen and vacuum systems only, solder joints may be
used. Completely clean off excess after brazing and soldering.
SECTION 15217N
Page 26