TABLE 2 - MONITOR AND SAFETY CONTROL SCHEDULE
Light
and
Indicating
Item
Shutdown
Alarm
Light Only
5.
High Lube Oil Temperature
Yes
Yes
-
6.
Low Lube Oil Pressure
Yes
Yes
-
7.
Low Oil Reservoir Level
No
Yes
-
8.
High Condensate Level Intercooler
Yes
Yes
-
(wired to one light)
9.
High Motor Stator Temperature
Yes
Yes
-
10. High Condensate Level Aftercooler
No
No
Yes
11. High Inlet Pressure Drop Across
No
Yes
-
3 stage)
12. High CO Level
Yes
Yes
-
2.3.5.4
Monitoring Instruments
Provide the following monitoring instruments in addition to the monitor and
safety controls. Pressure gages shall conform to ASME B40.1, 115 mm 4 1/2
inch diameter, red marking pointer, single bourdon tube, brass case, black
stainless steel barstock needle isolation valve. Thermometers shall be
extended stainless steel sheathed bimetallic stem, 90 mm 3 1/2 inch dial,
and separable 100 mm 4 inchstainless steel wells. Temperature measurements
at inaccessible locations shall be made with remote reading thermometers
conforming to MIL-T-19646, Class C separable well of Type 304 stainless
steel. Select pressure and temperature gage ranges to give a normal
operating reading near the midpoint of the scale range.
a.
Oil cooler outlet temperature gages for oil.
b.
Oil cooler inlet and outlet temperature gages for water.
c.
Lubrication oil pump discharge pressure gage.
d.
Pa 8, zero, 8 inch water gage. Provide selector valve, tubing,
and tap to measure static gage pressure downstream of each filter
stage.
e.
Total running time readout.
f.
Interstage air pressure gages for each interstage.
g.
h.
Cooling water return from compressor pressure gage.
i.
SECTION 15214N
Page 17