TABLE 2 - MONITOR AND SAFETY CONTROL SCHEDULE
Light
and
Indicating
Item
Shutdown
Alarm
Light Only
7.
Low Cooling Water Flow
No
Yes
-
8.
Low Oil Reservoir Level
No
Yes
-
9.
High Condensate Level Each Intercooler
Yes
Yes
-
10. Vibration Monitors Each Pinion
Yes
Yes
-
11. Surge Limit Approach
Yes
Yes
-
12. High Motor Stator Temperature
Yes
Yes
-
13. High Condensate Level Aftercooler
No
No
Yes
14. High Inlet Pressure Drop Across
No
Yes
-
15. High CO Level
Yes
Yes
-
2.3.5.6
Monitoring Instruments
Provide the following monitoring instruments in addition to the monitor and
safety controls. Pressure gages shall conform to ASME B40.1, 115 mm 4 1/2
inch, red marking pointer, single bourdon tube, brass case, black enamel
finish. Provide pressure gages with a pressure snubber and a stainless
steel barstock needle isolation valve. Thermometers shall be extended
stainless steel sheathed bimetallic stem, 90 mm 3 1/2 inch dial, and
separable 100 mm 4 inch stainless steel wells. Temperature measurements at
inaccessible locations shall be made with remote reading thermometers
conforming to MIL-T-19646, Class C separable well of Type 304 stainless
steel. Select pressure and temperature gage ranges to give a normal
operating reading near the midpoint of the scale range.
a.
Oil cooler outlet temperature gages for oil.
b.
Oil cooler inlet and outlet temperature gages for water.
c.
Lubrication oil pump discharge pressure gage.
d.
Compressor seal air pressure gage, if applicable.
e.
Pa 8, zero, 8 inch water gage. Provide selector valve, tubing,
and tap to measure static gage pressure downstream of each filter
stage.
f.
Pinion shaft vibration monitor readout with stage selection switch.
g.
Total running time readout.
h.
i.
Cooling water return from compressor pressure gage.
SECTION 15213N
Page 17