UFGS-15184N (September 1999)
------------------------------
Preparing Activity: NAVFAC
Replacing without revision
NFGS of same number and date
UNIFIED FACILITIES GUIDE SPECIFICATIONS
References are in agreement with UMRL dated 23 June 2005
**************************************************************************
SECTION 15184N
[HIGH][MEDIUM] TEMPERATURE WATER SYSTEM WITHIN BUILDINGS
09/99
**************************************************************************
NOTE: This guide specification covers the
requirements for high and medium temperature water
including connections to interior existing piping
and system terminal unit.
Comments and suggestions on this guide specification
are welcome and should be directed to the technical
proponent of the specification. A listing of
technical proponents, including their organization
designation and telephone number, is on the Internet.
Recommended changes to a UFGS should be submitted as
a Criteria Change Request (CCR).
Use of electronic communication is encouraged.
Brackets are used in the text to indicate designer
choices or locations where text must be supplied by
the designer.
**************************************************************************
**************************************************************************
NOTE: Project requirements may require addition of
supplemental information to the paragraphs contained
herein, however, designer is cautioned to verify
additional references to ascertain applicability of
materials to system design prior to inclusion.
**************************************************************************
**************************************************************************
NOTE: The following information shall be shown on
1. Flow diagram of high or medium temperature water
piping indicating connections to existing supply and
return, pressure and temperature of existing supply
and return, (maximum and minimum or constant,
applicable), valves and critical valve positions
(including normally closed for bypass valve), any
necessary flow rates, pressure drops not already in
SECTION 15184N
Page 3