2.5.3
Motor Starters
**************************************************************************
NOTE: The motor control requirements should be
coordinated with Section 16402, "Interior Wiring
Systems" and will depend on field conditions. The
following types of motor starters should be used as
a guide only. When electrical equipment is
connected to heavily loaded power circuits, the
starting current may cause an excessive voltage drop
on the circuit.
Motor kW
Voltage
Type Starter
Up to 5.50
208-230
Across-the-line-magnetic
5.50 to 11
208-230
Across-the-line-magnetic, part winding
or wye-delta
Motor h.p.
Voltage
Type Starter
Up to 7 1/2
208-230
Across-the-line-magnetic
7 1/2 to 15
208-230
Across-the-line-magnetic, part winding
or wye-delta
**************************************************************************
NEMA ICS 2, [manual] [across-the-line magnetic,] [reduced voltage-start]
[part-winding] [wye-delta] type with NEMA ICS 6 [general purpose]
[weather-resistant] [water tight] enclosure.
2.6
2.6.1
Finned Tube Radiation Units
[FS S-R-2834, steel tube with steel fins,] [FS A-A-50545, copper tube with
aluminum fins,] [with an adjustable damper,] size and capacity not less
than indicated.
2.6.2
FS A-A-50545, size and capacity not less than indicated.
2.6.3
Convectors
FS A-A-50543, FS A-A-50544, design and capacity not less than indicated.
2.7
**************************************************************************
NOTE: For LANTNAVFACENGCOM projects, refer to
LANTNAVFACENGCOM regional 15700, "Heating,
**************************************************************************
Heating and ventilating units for steam system shall be as specified in
[Section 15720N AIR HANDLING AND DISTRIBUTION EQUIPMENT,] except that steam
coils shall be provided in lieu of water coils. Coils for factory