TABLE 1B
Class II Vibration Isolator Types and Minimum Static Deflection
(MSD, mm) for basements below grade and floor slabs on earth
Equipment
Type (Note (1))
MSD
Tubular Centrifugal
and Axial Fans
(Note (2))
Suspended
H with deflections specified for
centrifugal blowers
Floor Mounted
Arrangements 1 & 9
NM
8.89
Utility Fans
(Note (2))
Suspended and
H with deflections specified for
centrifugal
Floor Mounted
NM
8.89
High-Pressure Fans
HR recommended for minimizing
(Over 1494 Pa
undesirable thrust effects
Static Pressure)
and Other
Machines
Producing Thrust
(Note (2))
Engines and Engine
Driven Equip
750 rpm and over
S
25.40
Dimmer Banks and
Up to 454 kg
NP
6.35
NM
8.89
Over 454 kg
SV
25.40
NOTES:
Note (1) and Note (2) are same as for TABLE 1A.
TABLE 1B
Class II Vibration Isolator Types and Minimum Static Deflection
(MSD, inches) for basements below grade and floor slabs on earth
Equipment
Type (Note (1))
MSD
Absorption Refrigeration
NP
0.25
Machines
NM
0.35
SECTION 15070N
Page 19