TABLE 1B
Class II Vibration Isolator Types and Minimum Static Deflection
(MSD, mm) for basements below grade and floor slabs on earth
Equipment
Type (Note (1))
MSD
NP
6.35
NM
8.89
Pumps
Closed Coupled
NP
6.35
Up to 5 1/2 kW
NM
8.89
Over 5 1/2 kW
S-I
25.40
Base Mounted
Up to 15 kW
S-I
25.40
15 to 56 kW
S-I
25.40
Over 56 kW
S-I
25.40
NP
6.35
NM
8.89
Factory Assembled Air
AC and HV Units
(Note (2))
Suspended Units
Up to 3 3/4 kW
H
25.40
Over 3 3/4 kW
Up to 400 rpm
H
44.45
Over 401 rpm
H
25.40
Floor Mounted Units
Up to 3 3/4 kW
NP
6.35
NM
8.89
Over 3 3/4 kW
Up to 400 rpm
NM
8.89
Over 401 rpm
NM
8.89
Centrifugal Blowers
175 - 224 rpm
NM-B
8.89
225 - 299 rpm
NM-B
8.89
300 - 374 rpm
NM-B
8.89
375 - 499 rpm
NM-B
8.89
Over 500 rpm
NM-B
8.89
SECTION 15070N