d.
"FIRE DEPARTMENT" key switch, with "OFF-HOLD-ON" positions, in
that order with key removable in all positions. Provide fire sign
or jewel and audible signal device, in accordance with ASME A17.1
Figure 211.3a. Both visual and audible signals are activated when
Phase I key switch in hall is activated or when smoke detector
activates return of elevator(s) to main fire response floor.
Visual and audible signal shall remain activated until car has
reached designated or alternate fire response floor. Upon arrival
at fire response floor visual signal remains illuminated and
audible signal becomes silent.
e.
Emergency two-way communication. Provide momentary pressure,
single illuminating pushbutton operated communication device that
complies with ASME A17.1, UFAS, and the Americans with
Disabilities Act.
[f.
Key-operated on-off "HOSPITAL EMERGENCY COMMANDEERING SERVICES"
switch.]
**************************************************************************
NOTE: Omit the following paragraph, "...phone
jack," unless specifically requested by the activity.
**************************************************************************
[g.
Sound-actuated firefighter phone jack.]
2.5.4.2
Service Controls
a.
Inspection switch that transfers car control to top-of-car
inspection operating controls and prevents car operation from
in-car control panel.
b.
Independent service switch.
c.
Two car light switches, one for light in car and one for lights on
top and bottom of car frame.
d.
Fan switch, two-speed.
e.
Infra-red curtain unit cutout switch.
f.
120-volt ac 60 Hz single-phase duplex electrical outlet of
ground-fault-circuit-interrupt (GFCI) design.
g.
Communication device between car and elevator machine room.
[
h.
Parking switch.]
**************************************************************************
NOTE: Use for power-operated doors and gate.
**************************************************************************
[
i.
"DOOR OPEN" and "DOOR CLOSE" buttons.]
2.5.4.3
Certificate Window
Provide a minimum 100 mm high by 150 mm wide 4 inches high by 6 inches wide,
certificate window in car operating panel for elevator inspection
SECTION 14210N
Page 20