part of this specification) will be required for
each protected space. Such a system shall be
manually key operated, for fire department use only.
See also NFPA 12A section on relief venting.
**************************************************************************
**************************************************************************
NOTE: The following information should be shown on
the drawings:
locations of control panel, annunciator(s), audible
and visual alarm devices, manual actuation stations,
point of connection to the building fire evacuation
alarm system, remote trouble device, and point of
connection to the incoming power supply and fusible
safety switch. Do not show conduit sizes or number
of conductors for DC circuits. Do not show
2. Show single line riser diagram for all
detection, activation, and alarm circuits.
Connection of equipment shall be indicated by
circuit runs and not conduit runs. Do not indicate
number and size of conductors for interconnection of
fire alarm components.
for Halon storage containers. Show areas of system
coverage, with zone designations (if multiple
zones). Do not show Halon piping layout and nozzle
placement.
**************************************************************************
PART 1
GENERAL
1.1
REFERENCES
**************************************************************************
NOTE: Issue (date) of references included in
provided by the latest guide specification. Use of
SpecsIntact automated reference checking is
recommended for projects based on older guide
specifications.
**************************************************************************
The publications listed below form a part of this specification to the
extent referenced. The publications are referred to within the text by the
basic designation only.
ASME INTERNATIONAL (ASME)
ASME B16.11
(2002) Forged Fittings, Socket-Welding and
Threaded
ASME B16.3
(1998) Malleable Iron Threaded Fittings
SECTION 13966N
Page 4