Year 2000 (Y2K) Compliance Warranty
Contractor's material and test certificate; G
Pipe and fittings; G
SD-10 Operation and Maintenance Data
Refrigerated storage tank, Data Package 3; G
Hose reels, Data Package 3; G
Discharge nozzles, Data Package 2; G
Control panel, Data Package 3; G
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA. Submit copies of the manual after approval of
drawings, prior to training course, and [_____] calendar days
prior to date of beneficial occupancy.
SD-11 Closeout Submittals
As-built record drawings; G
1.7
QUALITY ASSURANCE
1.7.1
Qualifications
1.7.1.1
Installer Qualifications
Prior to installation, submit evidence including system type and design
showing that installer has successfully installed at least two low-pressure
carbon dioxide fire extinguishing systems conforming to the requirements of
NFPA and of the same type and design specified herein. Include names and
locations of the installations and written certification from the users
that the systems have performed satisfactorily for a period of not less
than 18 months.
**************************************************************************
NOTE: For projects administered by the Pacific
Division, Naval Facilities Engineering Command,
include the following optional paragraph requiring
the minimum qualification of a NICET Level-III
technician for preparation of all fire protection
system drawings.
**************************************************************************
[Qualifications of System Technician: Installation drawings, shop drawing
and as-built drawings shall be prepared, by or under the supervision of, an
individual who is experienced with the types of works specified herein, and
is currently certified by the National Institute for Certification in
Engineering Technologies (NICET) as an engineering technician with minimum
Level-III certification in Special Hazard System program. Contractor shall
submit data for approval showing the name and certification of all involved
individuals with such qualifications at or prior to submittal of drawings.]
SECTION 13962N