located on the exterior of the cabinet door or visible through the cabinet
door. Lamps shall be LED (Light Emitting Diode) type. Supervision will
not be required provided a fault in the annunciator circuits results only
of the remainder of the system. Each lamp shall provide specific
identification of the [zone] [area] [device] by means of a permanent label.
In no case shall zone identification consist of the words "Zone 1," "Zone
2," etc., but shall consist of the description of the [zone] [area]
[device].
2.3.1.2
Initiating Zones
**************************************************************************
NOTE: List zones from 1 to x, with a brief
description of each zone; e.g. "Zone 1: Aerosol
Storage Room." Expand this list as necessary to
identify all the zones required for the building.
Careful coordination with paragraph "System
Activation" and the number and location(s) of system
risers shown on drawings is required.
**************************************************************************
Shall be arranged as follows:
Zone 1:
[_____]
Zone 2:
[_____]
Zone 3:
[_____]
Zone x:
[_____]
2.3.1.3
Remote Annunciator Panel
**************************************************************************
NOTE: Coordinate location of remote trouble bell
and remote annunciator panel when both are provided.
Locate panel at or near the building entrance to
allow fire department quick access to panel.
**************************************************************************
Locate as shown. Panel shall duplicate all requirements specified for the
trouble lamps a single common system trouble lamp may be provided. Lamps
shall be LED (Light Emitting Diode) type, except lamps used in backlit
panels shall be LED or neon type. Panel shall have a lamp test switch.
Zone identification shall be by means of [permanently attached rigid
plastic or metal plate(s)] [silk-screened labels attached to the reverse
face of backlighted viewing window(s)]. Panel shall be of the [interior]
[weatherproof] type, [flush] [surface] [pedestal]-mounted.
2.3.2
2.3.2.1
Storage Batteries
**************************************************************************
NOTE: Consult the Public Works Department for
battery preference.
**************************************************************************
SECTION 13958N
Page 21