Annotate descriptive data to show the specific model, type, and
size of each item.
SD-05 Design Data
Sprinkler system design; G
Submit computer program generated hydraulic calculations to
Submit the name of the software program used.
SD-06 Test Reports
Preliminary tests on piping system; G
SD-07 Certificates
Qualifications of installer; G
Year 2000 (Y2K) Compliance Warranty; G
SD-10 Operation and Maintenance Data
[Deluge] [Preaction] valves, Data Package 3; G
Control panel, Data Package 3; G
Backflow preventer, Data Package 3; G
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
SD-11 Closeout Submittals
As-built drawings of each system; G
1.6
QUALITY ASSURANCE
1.6.1
Qualifications of Installer
Prior to installation, submit data showing that Contractor has successfully
installed systems of the same type and design as specified herein, or that
Contractor has a firm contractual agreement with a subcontractor having
such required experience. Data shall include names and locations of at
least two installations where the Contractor, or the subcontractor referred
to above, has installed such systems. Indicate type and design of each
system and certify that each system has performed satisfactorily in the
manner intended for not less than 18 months.
Qualifications of System Technician: Installation drawings, shop drawing
and as-built drawings shall be prepared, by or under the supervision of, an
individual who is experienced with the types of works specified herein, and
is currently certified by the National Institute for Certification in
Engineering Technologies (NICET) as an engineering technician with minimum
Level-III certification in Automatic Sprinkler System program. Contractor
SECTION 13945N