NOTE: Following information shall be shown on
1. Location and detail of each sprinkler system
supply riser, deluge or preaction valve, water motor
alarm, fire department inlet connection, control
panel, air compressor, fused disconnect switch, and
2. Location where each sprinkler system begins
including connection to water distribution system
piping.
3. Location of sprinkler system control valves,
post indicator valves, or wall indicator valves.
4. Area of sprinkler system coverage when system is
protecting partial areas.
5. Details of anchoring piping, including pipe
clamps and tie rods, or mechanical retainer glands.
6. Indicate existing sprinkler piping layout and
sprinkler heads on project drawings only if existing
sprinkler system is being modified and such layout
is necessary for clarity.
7. Do not show detector placement, conduit runs, or
number of conductors.
**************************************************************************
PART 1
GENERAL
1.1
REFERENCES
**************************************************************************
NOTE: Issue (date) of references included in
provided by the latest guide specification. Use of
SpecsIntact automated reference checking is
recommended for projects based on older guide
specifications.
**************************************************************************
The publications listed below form a part of this specification to the
extent referenced. The publications are referred to within the text by the
basic designation only.
AMERICAN WATER WORKS ASSOCIATION(AWWA)
AWWA C651
(1999) Disinfecting Water Mains
ASME INTERNATIONAL (ASME)
ASME A17.1
(2004) Handbook on Safety Code for
SECTION 13945N