SD-07 Certificates
Equipment
Certified copies of current applicable approvals or listings
issued by UL, FM or other nationally recognized testing laboratory
showing compliance with specified NFPA standards.
Installer[; G][; G, [_____]].
Written certificate of the installer's qualifications, as
specified.
SD-10 Operation and Maintenance Data
Central Fire Alarm System[; G][; G, [_____]].
step-by-step procedures required for system startup, operation,
and shutdown. The instructions shall include the manufacturer's
name, model number, service manual, parts list, and brief
description of the equipment and basic operating features.
[Six] [_____] copies of maintenance instructions listing routine
maintenance procedures, possible breakdowns and repairs and
troubleshooting guide. The instructions shall include conduit
layout, equipment layout, simplified wiring control diagrams of
the system as installed, and programming of DACT and DACR
equipment. Instructions shall be approved prior to training.
1.3
GENERAL REQUIREMENTS
1.3.1
Standard Products
Material and equipment shall be the standard products of a manufacturer
regularly engaged in the manufacture of digital alarm communicator systems
and shall be items that have been in satisfactory use for at least 2 years
prior to bid opening. Equipment shall be supported by a service
organization that can provide service within 24 hours.
1.3.2
Nameplates
Major components of equipment shall have the manufacturer's name, address,
type or style, voltage and current rating, and catalog number on a
noncorrosive and nonheat-sensitive plate which is securely attached to the
equipment.
1.3.3
Keys and Locks
Locks shall be keyed alike.
1.3.4
Tags
Tags with stamped identification number shall be furnished for keys and
locks.
1.3.5
Verification of Dimensions
The Contractor shall verify all dimensions in the field and shall advise
SECTION 13853A
Page 7