professional engineer, showing all points of connection. Diagram
shall include connections between monitoring center devices,
transmitter location appliances, control panels, supervised
devices, interfaces between building fire alarm equipment and
transmitting equipment, and all equipment that is activated or
controlled by the monitoring center equipment.
SD-03 Product Data
Battery
Substantiating battery calculations for supervisory and alarm
center system component and each transmitter panel component; and
the battery recharging periods shall be included. Battery
calculations shall substantiate both NFPA 72 and specification
requirements.
Spare Parts
Spare parts data for each different item of material and
equipment specified, not later than [_____] months prior to the
date of beneficial use. Data shall include a complete list of
parts and supplies with the current unit prices and source of
supply and a list of the parts recommended by the manufacturer to
be replaced after [1 year] [[_____] years] of service.
Registered Professional Engineer
Verification of experience and license number for Registered
Professional Engineer, as specified.
Training
Lesson plans and training data, in manual format, for the
training course. The operations training shall familiarize
designated Government personnel with proper operation of the
system. The maintenance training course shall provide the
designated Government personnel adequate knowledge required to
diagnose, repair, maintain, and expand functions inherent to the
system.
Test Procedures
Detailed test procedures, signed by the registered professional
engineer for the central fire alarm system [30] [_____] days prior
to performing system tests. The test procedures shall be signed
by the Registered Professional Engineer.
SD-06 Test Reports
Testing
Test reports in booklet form showing field tests performed to
prove compliance with the specified performance criteria, upon
completion and testing of the installed system. Each test report
shall document readings. test results, and indicate the final
position of controls.
SECTION 13853A
Page 6