rating of each visible notification appliance.
1.6.4.2
modules, relays, switches and lamps in the control panel.
1.6.4.3
System As-Built Drawings
**************************************************************************
NOTE: Specify one set of as-built drawings unless
instructed otherwise by the EFD/EFA Fire Protection
Engineer.
**************************************************************************
Upon completion, and before final acceptance of the work, furnish to the
Contracting Officer [_____] complete set[s] of as-built drawings [,
including complete as-built circuit diagrams,] of [each] [the] system. The
as-built drawings shall be "D" size 850 by 550 mm 34 by 22 inches
reproducible drawings on mylar film drawn to the same scale as the contract
drawings and with title block similar to contract drawings. The as-built
drawings shall be furnished in addition to the record drawings required by
Division 01.
1.6.5
UL Listing or FM Approval
Submit copies of UL listing or FM approval data showing compatibility of
the smoke detector model being provided with the control panel being
provided, if 2-wire detectors are proposed for use.
1.7
MAINTENANCE
1.7.1
Spare Parts
Furnish the following spare parts:
a.
5 complete sets of system keys
b.
1 of each type of audible and visual alarm device installed
c.
2 of each type of fuse required by the system
[d.
[_____] spare zone modules for modular type control panels in
addition to those installed in the panel]
[e.
2 of each type of heat detector installed]
[f.
2 of each type of smoke detector base and head installed]
[g.
1 smoke detector manufacturer's test screen, card or magnet for
each 10 detectors, or fraction thereof, installed in the system]
1.7.2
Manuals
Submit operation and maintenance data in accordance with Section 01781
OPERATION AND MAINTENANCE DATA. Inscribe the following identification on
the cover: the words OPERATION AND MAINTENANCE MANUAL, the location of the
building, the name of the Contractor, system manufacturer and the contract
SECTION 13852N
Page 13