The Contractor or installer shall have satisfactorily installed fire alarm
systems of the same type and design as specified herein [and shall be UL
certified for the installation and testing of fire alarm systems].
Prior to commencing fire alarm system work, submit data showing that the
Contractor or installer has satisfactorily installed three fire alarm
systems of the same type and design as specified herein within the past
three years [and certify that each system has performed satisfactorily in
the manner intended for a period of not less than 18 months]. [Submit
proof of UL certification and a list of installer's personnel.]
For each system installed, submit the following:
a.
A detailed summary of the type and design of the system;
b.
The contract name or number, completion date of the project and
total cost of the system;
c.
The name and telephone number of the facility or installation for
whom the work was performed; and,
d.
The name and telephone number of a supervisory level point of
contact at the facility or installation who has knowledge of the
performance of the Contractor's or installer's work.
1.6.2
Manufacturer's Representative
Provide the services of a representative or technician from the
manufacturer of the system, experienced in the installation and operation
of the type of system being provided, to supervise installation,
adjustment, preliminary testing, and final testing of the system and to
provide instruction to Government personnel.
[1.6.3
Qualifications of System Technician
**************************************************************************
NOTE: For projects administered by PACNAVFACENGCOM
and SOUTHWESTNAVFACENGCOM, include the following
paragraph requiring the minimum qualification of a
NICET Level-III technician for preparation of all
fire protection system drawings.
**************************************************************************
Installation drawings, shop drawings and as-built drawings shall be
prepared by, or under the supervision of, a qualified technician.
Qualified technician shall be an individual who is experienced with the
types of work specified herein, and is currently certified by the National
Institute for Certification in Engineering Technologies (NICET) as an
engineering technician with minimum Level III certification in fire alarm
system program. Contractor shall submit data showing the name and
certification of the technician at or prior to submittal of drawings.
]1.6.4
Drawing Requirements
1.6.4.1
Submit shop drawings of the system floor plans showing locations of
initiating and indicating appliances and end-of-line supervisory devices.
Show wire color coding, wire counts, and device wiring order. Show candela